Slot: XLT
Percent reactance, L-T (winding 2 to winding 3). Use for 3-winding transformers only. On the kVA base of winding 1.
URI: dss:XLT
Applicable Classes
| Name |
Description |
Modifies Slot |
| Transformer |
A Transformer object in OpenDSS representing a multi-winding transformer conn... |
no |
Properties
Type and Range
Cardinality and Requirements
| Property |
Value |
| ### Slot Characteristics |
|
- Winding 2-to-3 leakage reactance, in percent, using the kVA base of winding 1 but the kV base of winding 2 (the lower- numbered winding of the 2-3 pair): zbase = kV_wdg2^2 * 1000 / kVA_wdg1. Import/export conversion is otherwise the same formula as XHL.
Annotations
Schema Source
- from schema: https://gridappsd.github.io/dss-graph/opendss
Mappings
| Mapping Type |
Mapped Value |
| self |
dss:XLT |
| native |
dss:XLT |
| close |
cim:TransformerMeshImpedance.x |
LinkML Source
name: XLT
annotations:
order:
tag: order
value: 19
description: Percent reactance, L-T (winding 2 to winding 3). Use for 3-winding transformers
only. On the kVA base of winding 1.
comments:
- 'Winding 2-to-3 leakage reactance, in percent, using the kVA base of winding 1 but
the kV base of winding 2 (the lower- numbered winding of the 2-3 pair): zbase =
kV_wdg2^2 * 1000 / kVA_wdg1. Import/export conversion is otherwise the same formula
as XHL.'
from_schema: https://gridappsd.github.io/dss-graph/opendss
close_mappings:
- cim:TransformerMeshImpedance.x
rank: 1000
owner: Transformer
domain_of:
- Transformer
range: float
required: false