Skip to content

Slot: XLT

Percent reactance, L-T (winding 2 to winding 3). Use for 3-winding transformers only. On the kVA base of winding 1.

URI: dss:XLT

Applicable Classes

Name Description Modifies Slot
Transformer A Transformer object in OpenDSS representing a multi-winding transformer conn... no

Properties

Type and Range

Property Value
Range Float
Domain Of Transformer

Cardinality and Requirements

Property Value
### Slot Characteristics
Property Value
Owner Transformer

Comments

  • Winding 2-to-3 leakage reactance, in percent, using the kVA base of winding 1 but the kV base of winding 2 (the lower- numbered winding of the 2-3 pair): zbase = kV_wdg2^2 * 1000 / kVA_wdg1. Import/export conversion is otherwise the same formula as XHL.

Identifier and Mapping Information

Annotations

property value
order 19

Schema Source

  • from schema: https://gridappsd.github.io/dss-graph/opendss

Mappings

Mapping Type Mapped Value
self dss:XLT
native dss:XLT
close cim:TransformerMeshImpedance.x

LinkML Source

name: XLT
annotations:
  order:
    tag: order
    value: 19
description: Percent reactance, L-T (winding 2 to winding 3). Use for 3-winding transformers
  only. On the kVA base of winding 1.
comments:
- 'Winding 2-to-3 leakage reactance, in percent, using the kVA base of winding 1 but
  the kV base of winding 2 (the lower- numbered winding of the 2-3 pair): zbase =
  kV_wdg2^2 * 1000 / kVA_wdg1. Import/export conversion is otherwise the same formula
  as XHL.'
from_schema: https://gridappsd.github.io/dss-graph/opendss
close_mappings:
- cim:TransformerMeshImpedance.x
rank: 1000
owner: Transformer
domain_of:
- Transformer
range: float