Skip to content

Slot: MVAsc1

MVA Short Circuit, 1-phase fault. Used to derive zero-sequence impedance.

URI: dss:MVAsc1

Applicable Classes

Name Description Modifies Slot
Vsource A Vsource object in OpenDSS representing an ideal voltage source (slack bus) ... no

Properties

Type and Range

Property Value
Range Float
Domain Of Vsource

Cardinality and Requirements

Property Value
### Slot Characteristics
Property Value
Owner Vsource

Comments

  • Import fallback, used only when R1/X1/R0/X0 are not all given and MVAsc3 > 0: Zs = basekv² / MVAsc1; Z0 = 3×Zs − 2×Z1; r0 = Z0 / √(1 + x0r0²); x0 = r0 × x0r0 (x0r0 defaults to 3.0 if not specified). If MVAsc1 is absent, r0/x0 default to r/x instead. Not stored directly on CIM; r0/x0 are the canonical fields and are always written back on export via R0/X0 — MVAsc1 itself is not exported.

Identifier and Mapping Information

Annotations

property value
order 8

Schema Source

  • from schema: https://gridappsd.github.io/dss-graph/opendss

Mappings

Mapping Type Mapped Value
self dss:MVAsc1
native dss:MVAsc1
close cim:EnergySource.r0, cim:EnergySource.x0

LinkML Source

name: MVAsc1
annotations:
  order:
    tag: order
    value: 8
description: MVA Short Circuit, 1-phase fault. Used to derive zero-sequence impedance.
comments:
- 'Import fallback, used only when R1/X1/R0/X0 are not all given and MVAsc3 > 0: Zs
  = basekv² / MVAsc1; Z0 = 3×Zs  2×Z1; r0 = Z0 / √(1 + x0r0²); x0 = r0 × x0r0 (x0r0
  defaults to 3.0 if not specified). If MVAsc1 is absent, r0/x0 default to r/x instead.
  Not stored directly on CIM; r0/x0 are the canonical fields and are always written
  back on export via R0/X0  MVAsc1 itself is not exported.'
from_schema: https://gridappsd.github.io/dss-graph/opendss
close_mappings:
- cim:EnergySource.r0
- cim:EnergySource.x0
rank: 1000
owner: Vsource
domain_of:
- Vsource
range: float
required: false