Slot: MVAsc1
MVA Short Circuit, 1-phase fault. Used to derive zero-sequence impedance.
URI: dss:MVAsc1
Applicable Classes
| Name |
Description |
Modifies Slot |
| Vsource |
A Vsource object in OpenDSS representing an ideal voltage source (slack bus) ... |
no |
Properties
Type and Range
Cardinality and Requirements
| Property |
Value |
| ### Slot Characteristics |
|
- Import fallback, used only when R1/X1/R0/X0 are not all given and MVAsc3 > 0: Zs = basekv² / MVAsc1; Z0 = 3×Zs − 2×Z1; r0 = Z0 / √(1 + x0r0²); x0 = r0 × x0r0 (x0r0 defaults to 3.0 if not specified). If MVAsc1 is absent, r0/x0 default to r/x instead. Not stored directly on CIM; r0/x0 are the canonical fields and are always written back on export via R0/X0 — MVAsc1 itself is not exported.
Annotations
Schema Source
- from schema: https://gridappsd.github.io/dss-graph/opendss
Mappings
| Mapping Type |
Mapped Value |
| self |
dss:MVAsc1 |
| native |
dss:MVAsc1 |
| close |
cim:EnergySource.r0, cim:EnergySource.x0 |
LinkML Source
name: MVAsc1
annotations:
order:
tag: order
value: 8
description: MVA Short Circuit, 1-phase fault. Used to derive zero-sequence impedance.
comments:
- 'Import fallback, used only when R1/X1/R0/X0 are not all given and MVAsc3 > 0: Zs
= basekv² / MVAsc1; Z0 = 3×Zs − 2×Z1; r0 = Z0 / √(1 + x0r0²); x0 = r0 × x0r0 (x0r0
defaults to 3.0 if not specified). If MVAsc1 is absent, r0/x0 default to r/x instead.
Not stored directly on CIM; r0/x0 are the canonical fields and are always written
back on export via R0/X0 — MVAsc1 itself is not exported.'
from_schema: https://gridappsd.github.io/dss-graph/opendss
close_mappings:
- cim:EnergySource.r0
- cim:EnergySource.x0
rank: 1000
owner: Vsource
domain_of:
- Vsource
range: float
required: false